ABB ACS530变频器与DCS通讯参数设置
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHBzL2ltYWdlMTA5LjM2MGRvYy5jbi9Eb3dubG9hZEltZy8yMDIwLzEyLzA0MjEvMjA5MDYyMjU5XzFfMjAyMDEyMDQwOTEwNTEyMTI=.jpg)
一、硬件接线
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHBzL2ltYWdlMTA5LjM2MGRvYy5jbi9Eb3dubG9hZEltZy8yMDIwLzEyLzA0MjEvMjA5MDYyMjU5XzJfMjAyMDEyMDQwOTEwNTEzMjE=.jpg)
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHBzL2ltYWdlMTA5LjM2MGRvYy5jbi9Eb3dubG9hZEltZy8yMDIwLzEyLzA0MjEvMjA5MDYyMjU5XzNfMjAyMDEyMDQwOTEwNTE0MzE=.jpg)
DCS柜(K-PAT01-D+/D-)与变频器连接(B+/A-)
二、变频器参数设置
1、中英文设置96.01=2052;
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHBzL2ltYWdlMTA5LjM2MGRvYy5jbi9Eb3dubG9hZEltZy8yMDIwLzEyLzA0MjEvMjA5MDYyMjU5XzRfMjAyMDEyMDQwOTEwNTE2MTg=.jpg)
2、启用MODBUS RTU功能58.01=1;
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHBzL2ltYWdlMTA5LjM2MGRvYy5jbi9Eb3dubG9hZEltZy8yMDIwLzEyLzA0MjEvMjA5MDYyMjU5XzVfMjAyMDEyMDQwOTEwNTE5MzE=.jpg)
3、设置变频器通讯地址58.03=11;
![](http://pic.ikafan.com/imgp/L3Byb3h5L2h0dHAvaW1hZ2UxMDkuMzYwZG9jLmNuL0Rvd25sb2FkSW1nLzIwMjAvMTIvMDQyMS8yMDkwNjIyNTlfNl8yMDIwMTIwNDA5MTA1MjQw.jpg)
4、变频器通讯波特率设置58.04=3(19.2kbit/s)
![](http://n4.ikafan.com/assetsj/blank.gif)
5、变频器设置通讯校验方式58.05=2(偶校验,1停止位)
![](http://n4.ikafan.com/assetsj/blank.gif)
6、变频器通讯控制设置5806=0(已启用,正常运行)
![](http://n4.ikafan.com/assetsj/blank.gif)
7、变频器寻址方式默认选择58.33=0(默式0)
![](http://n4.ikafan.com/assetsj/blank.gif)
8寄存器地址参考
![](http://n4.ikafan.com/assetsj/blank.gif)
访问的地址为:
40106 输出频率
40107 电机电流
40111 直流电压
三 \DCS参数设置
![](http://n4.ikafan.com/assetsj/blank.gif)
1、和利时DCS(K系列)通讯模块设置
![](http://n4.ikafan.com/assetsj/blank.gif)
2、添加直流电压地址:40111
![](http://n4.ikafan.com/assetsj/blank.gif)
3、测试结果
![](http://n4.ikafan.com/assetsj/blank.gif)
赞 (0)